Station Setup
2300 Connect via 2100-IS

The 2100-IS is an isolated to RS485 converter, with comms timeout relay.

2100-IS to 2300-XX connections (See 2300-XX Manual for complete wiring diagram)

2100-IS Terminal 2300-XX Terminal
70 70
71 71

Fit a 1K terminating resistor at the end of the data loop.

2100-IS Dip Switch Settings for RS485 operation - Dip Switch S2

Switch State
1 ON
2 ON
3 ON
4 ON
5 OFF
6 As Required for Alarm Delay
7 OFF *
8 OFF

*Set switch 7 ON for improved TXE turn off performance IF Comms Delay in 2300-XX stations has been cleared from the default value of 20 mSec.