| FAQ |
| Doing Station Find on 2300-XX stations |
When doing a Find Stations on 2300-XX stations, the TX and RX leds on the station will only flash when a valid command has been detected by the station (thus a read of data of station number matching the address set at the dip switches).
This is unlike the 2100-XX stations, the RX leds on the stations flash for ANY station commands on a data loop, and only when a valid command is detected will the TX and RX leds flash together.
For a 2300-XX station at node 2
| Station | LED flash |
| 0 | No |
| 1 | No |
| 2 | RX, TX flash |
| 3 | No |
For a 2100-XX station at node 2
| Station | LED flash |
| 0 | RX Flash |
| 1 | RX Flash |
| 2 | RX, TX flash |
| 3 | RX Flash |