FAQ |
Using Kinematics Serial Converters with Modbus PLCs |
The Kinematics serial converter 2199-801 converters where used on site to
talk to modbus ascii & modbus RTU devices (one converter for rtu, another
for ascii).
Notes:
1. The converter has built in 120 ohm terminating resistors. Do not place or
turn on terminators in the middle of a data loop, put on only those devices at
the end. If at all possible use a daisy chain connection as opposed to a star or
a line with long spurs.
2. Follow the wiring diagram CAREFULLY as the terminals have a strange wiring
order:
Labeled on converter
2 TX+
1 TX-
3 RX+
4 RX-
5 Screen
3. The Screen is an 0V connection so connect to 0V or signal ground at the other
end.
If you see the RX light "glow", it means that sufficient noise is causing
a signal to appear on the rx lines. Check the OV or screen is connected from the
converter to the PLC.
4. If comms is randomly bad, check the modbus addresses of each device is unique
as some collisions will occur if two devices are set to the same number (ie data
from one plc will be mixed up with another).
Also check modbus addresses if the system is setup for a number of devices and
some of those devices are not responding.
5. If the Modbus ASCII driver detects the wiring is reversed it will state the error "Break Received", as it can't decode the characters properly.