Checklist for using Shimaden SR23/FP23 with MicroScan

Shimaden Controller Settings

Comms settings needed:
PROT SHIMADEN
ADDR As Needed (unique address for each controller)
BPS 9600
MEM EEP

DATA 8
PARI NONE
STOP 1
DELY 25 (may need to be longer depending on your converter).

CTRL STX_ETX_CR
BCC ADD

Alternatively
DATA 7
PARI EVEN
STOP 1
DELY 25

Using MicroScan Converter

Use cable supplied with converter to connect to computer.
The TX and TXE leds light up (at minimum when the comms is working, and RX when the controller responds).

Set S2 1,2,3,4 ON.

Do Not use a terminating Resistor at the end of the coms line.

Connections

70     -
71     +
74     SG