FAQ |
Checklist for using Shimaden SR23/FP23 with MicroScan |
Shimaden Controller Settings
Comms settings needed:
PROT SHIMADEN
ADDR As Needed (unique address for each controller)
BPS 9600
MEM EEP
DATA 8
PARI NONE
STOP 1
DELY 25 (may need to be longer depending on your converter).
CTRL STX_ETX_CR
BCC ADD
Alternatively
DATA 7
PARI EVEN
STOP 1
DELY 25
Using MicroScan Converter
Use cable supplied with converter to connect to computer.
The TX and TXE leds light up (at minimum when the comms is working, and RX when the controller responds).
Set S2 1,2,3,4 ON.
Do Not use a terminating Resistor at the end of the coms line.
Connections
70 -
71 +
74 SG