Key Steps when adding new stations to MicroScan (Version 4 and 5) |
When adding new stations to MicroScan:
Version 4:
Start Setup Manager
Click Recorder Setup
Click Program Address
Enter the Station Serial Number (written on lid of station)
Enter a new station number (the next free station number, such as 2 if 1 station
already on site, or three if two stations already in use)
Click Program to program the station number to the station.
Use Program Station Setup to configure the station.
Use Find Stations (System Setup, MicroScan Interface, Find Stations to look for stations on the data loop).
Version 5:
On Setup Tools, Use Add Station Wizard to add the station to the system, the wizard will auto allocate the next free station number for you.
Use Program Station Setups to configure the station.
Use Find Stations (MicroScan Interface link, Find Stations) to find stations on a data loop.
When Version 5 starts assigning station numbers, it starts at station 2, the next station to be added will be 3 and the next 4 etc. This prevents conflicts when new factory programmed stations are added to an existing data loop.
Station Lights:
When adding a station, the stations RX led should always flash to indicate
data is being sent (it is normally OFF and flashes on when data is present).
If this LED does not flash it indicates incorrect wiring, short circuits or the
computer is not sending out data (i.e MicroScan not running).