Recorder Quick Setup
Station Connections

RS 232

If the station is RS232, it is connected directly to a COM port on the computer using the supplied RJ-11 gray cable and 9 pin connector.

RS 422

If the station(s) are RS422 they are connected via a 4 core cable to a 2100-IS, or 2100-NS, which is then connected to the COM port of the computer. Power is applied to 2100-IS, 2100-NS via supplied plug pack or to IN2000-IS via mains supply.

RS 422 Connections

2100-NS, 2100-IS 2100-XX station
70 70
71 71
72 72
73 73

The 2100-IS, NS is linked for RS422 operation. The station comms links are in L1,L2.
The cable should be low capacitance data cable. It can be up to 1200m in length.

RS 485

If the station(s) are RS485 they are connected via a 2 core cable to a 2100-IS, or 2100-NS, which is then connected to the COM port of the computer. Power is applied to 2100-IS, 2100-NS via supplied plug pack or to IN2000-IS via mains supply.

RS 485 Connections

2100-NS, 2100-IS 2100-XX station
70 70
71 71

The 2100-IS, NS is linked for RS485 operation. The station comms links are in L3,L4.
The cable should be low capacitance data cable. It can be up to 1200m in length.