ZigBee Wireless Data Links  
Base / Remote DIP Switch B  

Base/Remote Function Selection.

Switch

Meaning

OFF

ON

1

Parity Selection

None *

Even

2

Protocol Selection

ASCII
2100/2400 Stations

Modbus RTU
2300 Stations

3

Base/Remote Selection

Base

Remote **

4

Transparent

Non Trans *

Transparent

5

Connections

Sleepers Only

All Types (Remotes + Sleepers)

6

RS485 Termination

N/C *

ON

7

RS485 Bias Gnd

N/C *

ON

8

RS485 Bias Vcc

N/C *

ON

* always OFF for use with Microscan.
* when using sleepers only, set both DIP Switch 2 and 5 OFF.
** Do not use Remote (Switch 3 ON for Z-2400-TCP).

Example Settings Base

Base with Sleepers only (Small System)

Base with Sleepers + 2100-XX and Shimaden Controllers, Remotes

Base with 2300-XX Remotes (and sleepers if required). Remotes must also be set to Modbus mode.

Example Settings Remote

Remote with 2100-XX stations, Shimaden Controllers

Remote with 2300-XX stations (base must also set to modbus mode)