Related Products
SCADA software for industry and research.

2100-AO - Analogue Output Multiplexer for PLC; and Remote Station:

Discontinued Product Line

Product Specifications:

Download Installation Guide

Download Station Programmer Configuration Software

2100-AO
Click for large view

Features:

  • Cost Effective PLC Analogue Output Expansion.
  • 8 AO Require Only 7 PLC Digital Outputs.
  • Each Additional 2100-AO Used Requires Only 1 Extra PLC Digital Output.
  • 4, 8, or 12 bit AO Resolution Selectable.
  • BCD or Clock/Reset AO Channel Selectable.
  • 8 Analogue Outputs: mA or V.
  • 8 Analogue Inputs: mA or V.
  • 8 PID on Board Controllers - Future Development.
  • 12 Bit Resolution.
  • 12 Digitally Isolated, Optocoupler Inputs.
  • 4 Digital Inputs:
    • State or Count.
    • Speeds up to 50Hz.
  • 2 Digital, Mains Isolated, Relay Outputs.
  • 1 AI can be Demultiplexed to 8 AO.
  • 8 AI can be Multiplexed to 1 AO.
  • RS422/RS485 Up to 1200m.
  • RS232 Cost Effective Radio Installation.
  • RS232 Cost Effective PC or PLC AI or AO Expansion.
  • Selectable Baud Rates.
  • Easy Programming Via MicroScan Maps.
  • Programmable Station Number.
  • Programmable Relay States - NO or NC.
  • Comms Failure Time-out Using Relay 2.
  • Comms TXE and TX Delay Programming.
  • Programming Information Retained on Power Down.
  • Universal AC/DC Power Supply.
  • Easy to Install.
  • Compact DIN Rail Mount Enclosure.

Description:

This station provided economical analogue output expansion for PLC's plus was also designed for use as a Remote Station.

The 8 analogue outputs are factory configurable as 4~20mA, 0~20mA, 0~10Vdc, 2~10Vdc.

PLC Application:

The 2100-AO is driven by the PLC to determine the output channel and the output level. Here are 2 options for connecting between the PLC and 2100-AO.

Option 1: Using one analogue output from the PLC plus 4 on/off outputs.

Option 2: Using 7 on/off outputs from the PLC (no analogue output required).

For further details, please refer to the Installation Guide.

Connections for the 2100-AO

2100-AO connections

Terminals and Layout:

2100-AO terminals and layout