Recorder User Help |
Alarm Operation - Analogue Alarms |
The Recorder can perform High and/or Low alarm checking on a Lines
Value.
The line can be set to detect alarms in the following ways (using the Alarm Mode
setting, See Line Setup, Alarm
Mode, or Quick Setup, Alarm Mode),
|
The line has a setpoint and delay time for each alarm.
The temperature is monitored to see if it goes above the setpoint. Once above
the setpoint, the delay timer starts counting down, and when it expires, the
alarm has occurred. It is announced according to File Log, Global Notify,
Latch/Unlatch settings, and a relay can be turned on.
If the temperature goes above the setpoint, the delay timer starts. If the
temperature goes below the setpoint before the delay time expires, the alarm
delay time will be reset and will start again when the temperature goes above
the setpoint again. This allows for nuisance changes in value to be ignored such
as doors being opened and shut and defrost cycles, where the temperature will go
out of limits for short amounts of time, but is not sufficient to be considered
an alarm.
The alarm relay is controlled by the Latch Setting, see Latched
Alarm, Unlatched Alarm.
The temperature is monitored to see if it goes below the setpoint. Once below
the setpoint, the delay timer starts counting down, and when it expires, the
alarm has occurred. It is announced according to File Log, Global Notify,
Latch/Unlatch settings, and a relay can be turned on.
If the temperature goes below the setpoint, the delay timer starts. If the
temperature goes above the setpoint before the delay time expires, the alarm
delay time will be reset and will start again when the temperature goes below
the setpoint again. This allows the temperature to go out of limits for short
amounts of time, but is not sufficient to be considered an alarm.
The alarm relay is controlled by the Latch Setting, see Latched
Alarm, Unlatched Alarm.